Upcoming Russell Labs Building Power Outage

    Start:

    June 23rd at 4 a.m.

    Duration:

    Approximately four hours, could be less or more

    Warnings:

    • Do not enter the building until 8 a.m. June 23rd. All the power will be off – including the building elevators.
    • Do not open refrigerators or freezers for any reason during the shutdown.
      • Includes individual, -80s, stand-alone, mini, and walk-in freezers

    Labs Should:

    Before June 23rd:

    • Make a game plan for what you need to shut off on Monday the 22nd in order to not lose any data or samples or media.
      • Include shutting down any computers or servers in the lab.
    • Communicate the plan to your lab members so everyone on the same page for this.
    • For ultra-low freezers, clear out the frost from the door seals.

    On June 23rd, after power is restored:

    • Physically turn on any computers or servers in the lab.

    Facilities Will:

    • Turn off/on growth chambers, cold rooms, -80 freezers, incubators and most everything else in the basement and some select items on other floors (RO and DI).

    Lab Fridges/Freezers:

    • If the lab fridge/freezer is plugged in, it will shut down when they cut the power, and it will automatically come back on when power is restored.
    • A new, full, -80 will retain critical temp for up to 36 hours, as long as the seals are kept free of frost build up and the door is kept shut.
      • Source: one of the largest distributors of ultra-low freezers in the Midwest.

    Concerns About Lab Equipment Being Damaged?

    • Use your best judgement.
    • Check the vendor’s website.